ASE Plus ™ AHU.
|
Specification
|
|
SPECIFICATION
Section 15xxx – ASE Plus™
Air Handling Units - Factory Fabricated
Part 1 – General
1.1
Related Documents
A.
General: Comply with the General Conditions and all applicable
contract documents.
1.2
Work Included -
Furnish all labor, material, facilities and tools for a complete and proper
installation. The work of this Section shall include but not be limited to the
following:
A.
Air handling units.
B.
Related
work specified elsewhere:
1.
Supports and anchors
2.
Meters and gauges
3.
Mechanical insulation
4.
Hydronic piping systems
5.
Steam and condensate piping and specialties
6.
Refrigerant piping and specialties
7.
Sheet metal ductwork
8.
Sound attenuators
9.
Air terminal units
10.
Automatic temperature control systems
11.
Testing, adjusting and balancing
12.
Starters
13.
Power wiring
1.3
Submittals
A.
Product Data:
Submit manufacturer’s technical product data for air handling units showing
dimensions, weights, capacities, ratings, certified fan performance curves, with
operating point clearly indicated, motor electrical characteristics, and
finishes of materials, and installation instructions.
B.
Shop
Drawings: Submit
shop drawings showing unit dimensions, weight loading, required clearances,
field connection details and methods of support. Draw to a scale of 3/8” to one
foot, using same sheet size as contract drawings. Include dampers and duct
connections.
C.
Maintenance
Data: Submit
maintenance instructions, including instructions for lubrication, filter
replacement, motor and drive replacement, and spare parts list. Include this
data, product data, shop drawings, and wiring diagrams in operating and
maintenance manuals; in accordance with requirements of Division 1.
1.4
Quality Assurance
A.
Manufacturer’s Responsibility:
Provide factory designed and fabricated air handling units. Unit manufacturer
shall have sole source responsibility for the design, factory fabrication and
supply of all air handling unit components and equipment as noted below.
Provide air handling units that are a product of an equipment manufacturer
regularly engaged in the production of such units. Unit components and equipment
fabricated and supplied by the contractor will not be permitted.
B.
Contractor’s Responsibility:
The Contractor shall be responsible for the installation of the air handling
unit per the instructions and submittal documents supplied by the unit
manufacturer. The Contractor shall be responsible for providing and installing
damper actuators and linkage, electrical equipment, wiring and piping. The
Contractor shall provide the unit manufacturer with all field dimensions,
mounting locations and duct openings as required to coordinate the design and
fabrication of the unit.
C.
Certifications:
Provide certified ratings of units based on tests performed in accordance with
ARI 430, “Central-Station Air Handling Units”.
D.
Codes and
Standards:
Provide air handling units conforming to the following:
1.
Air Movement and Control Association, Inc. (AMCA): Comply with
applicable AMCA codes including AMCA 210 and 500.
2.
Air-Conditioning and Refrigeration Institute (ARI): Comply with
applicable ARI codes including ARI 410 and 430.
3.
American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE): Construct and install refrigerant coils in accordance with ASHRAE 15,
“Safety Code for Mechanical Refrigeration”.
4.
National Electrical manufacturers Association (NEMA): Except for motors,
provide electrical components required as part of air handling units, which
comply with NEMA Standards.
5.
National Fire Protection Association (NFPA): Provide air handling unit
to comply with NFPA 90A, “Standard for the Installation of Air Condition and
Ventilating Systems”. Comply with NFPA 70, “National Electrical Code”, as
applicable for installation and electrical connections of ancillary electrical
components of air handling units.
6.
Sheet Metal and Air Conditioning Contractors’ National Association, Inc.
(SMACNA): Comply with applicable SMACNA standards including “HVAC Duct
Construction Standards - Metal and Flexible”.
7.
Underwriter’s Laboratories, Inc. (UL): Except for motors, provide
electrical components required as part of air handling units, which have been
listed and labeled by UL.
1.5
Delivery, Storage and Handling
A.
Delivery:
Deliver air handling unit components on factory-installed shipping skids; pack
small components in factory-fabricated protective containers.
B.
Handling:
Handle air handling unit components carefully to avoid damage to components,
enclosures, and finishes. Do not install damaged components; replace and return
damaged components to air handling unit manufacturer.
C.
Storage:
Store air handling units in clean dry place and protect from weather and
construction traffic.
D.
Unloading:
Comply with manufacturer’s rigging and installation instructions for unloading
air handling unit components, and moving units to final location.
Part
2 – Product
2.1
Manufacturers
A.
Acceptable manufacturers: Vibro-Acoustics
2.2
Air Handling Units
A.
General:
The physical dimensions of the air handling unit are important to the project.
Dimensions must be maintained as shown on the contract drawings, if dimensions
are different from that shown the owner and engineer must be advised at the time
of bid review. Scope of supply shall include wall and roof panels, access
doors, fans with motors, drives, vibration bases and isolators, coils with coil
racks, drain and drip pans, flexible connections, dampers, and silencers as
required by the contract drawings and schedules.
1.
Design unit fans and casings, which are suitable for the maximum, total
static pressure of the fans under all conditions.
B
Acoustical
Performance: The
maximum generated sound pressure level of the air handling unit at all design
flows and pressure conditions shall not exceed sound levels that will provide a
( NC level as specified by engineer) in the (customer specified
location ). The air handling unit manufacturer shall provide sound
attenuators, baffles, acoustical material etc. as required to achieve
compliance. Provide data for all 8-octave bands
C.
Unit Construction
1.
Wall and Roof Panels: Panels shall be 4” tongue and groove type. The
exterior sheet shall be a minimum of 18 ga. galvanized steel. The interior
sheet shall be a minimum of 22 ga. galvanized steel. The interior sheet shall
be perforated in all areas, except downstream of the cooling coil and
humidifier. In these areas the interior sheet shall be 304 stainless steel for
a distance of 42”. Panels shall be insulated with 4” 3 lb./ft3
fiberglass.
2.
Removable Panels: Bolted panels shall be provided for fan and coil
removal. Panels shall be 4” with construction as noted above.
3.
Media: Media shall be incombustible, acoustical quality, shot-free
fiberglass insulation with long, resilient fibers bonded with a thermosetting
resin. Fiberglass shall be packed with 15% compression during panel assemble.
Media shall be bacteria and fungus resistant and conform to irregular surfaces.
Media shall not cause or accelerate corrosion of aluminum or steel. Mineral
wool will not be permitted as a substitute for fiberglass.
4.
Access Doors: Doors shall be provided for each component section. Doors
shall be 4” x 24” wide x 72” high with the same construction as the acoustic
panels, except that the interior sheet shall be solid. Doors shall be mounted
in a 10 ga. galvanized steel angle frame with a single “P” gasket. Hardware
shall include (2) cam-type latches and a stainless steel butt hinges. Doors
shall be supplied with 12” x 12” inspection windows, double glazed with ¼”
wire-reinforced glass mounted in a neoprene U-gasket.
5.
The acoustical performance of the panels shall be equal to or greater
than the following:
Octave Band,
Hz 125 250 500 1000
2000 4000
Transmission Loss, dB 21 27 37 48 55
55
Absorption
Coefficients 0.74 0.9 0.99 0.99 0.9 0.9
6.
The thermal conductance of the insulation shall be less than 0.06
BTU/hr/sq.ft./F at 50 degrees F mean temperature. The overall thermal
conductance of the assembled structure shall not exceed 0.15 BTU/hr/sq. ft./F at
50 degrees F mean temperature.
D.
Fans:
Provide fans conforming to AMCA 210 and rated for the duty noted in the air
handling unit schedule.
1.
Acceptable manufacturers: as specified
E.
Motors and
Drives: Provide
fan motors with a nameplate rating of not less than 10 percent above the fan
brake horsepower and drive loss at maximum capacities at any point on the
characteristic curve.
1.
Each motor provided with automatic control shall be capable of making
frequent starts as the control device may demand. Motors without automatic
control shall be capable of making not less than 4 starts per hour.
2.
Polyphase shall be of the dripproof, squirrel cage, induction type in
accordance with NEMA MG 1. Polyphase motors shall be single-voltage type or
increment starting type.
F.
Cooling and
Hot Water Coils
Coils shall be constructed
with 5/8” O.D. copper tubes with 0.020” tube wall thickness. Fins shall be
0.0075” aluminum. Coil casing shall be minimum of 16 ga. galvanized steel for
heating applications and 304 stainless steel for cooling applications. Headers
shall be non-ferrous barrels with vents and drain connections.
Coil connections are to be
extended through the casing wall by the unit manufacturer.
Coils shall be rated and
certified to carry the ARI stamp per ARI Standard 410-72.
Acceptable manufacturers:
as specified
G.
Coil Racks, Drain and Drip Pans
Coil racks shall be
constructed of 304 stainless steel. Coil racks shall be designed to permit the
removal of individual coil sections without disturbing remaining coils.
In cooling coil sections,
the drain pan shall be continuously welded, positively sloping 14 ga. 304
stainless steel pan with a minimum depth of 4” at the drain. The drain pan
shall be insulated with 2” 3 lb./ft3 fiberglass and an 18 ga.
galvanized steel cover.
Drip pans shall be
continuously welded, positively sloping 16 ga. 304 stainless steel with a
minimum depth of 2” at the drain. Drain piping shall be 304 stainless steel
with each drip pan individually piped to the drain pan.
H.
Filters
1.
Filters shall be 2” deep, medium efficiency, pleated, disposable type.
Each filter shall consist of a non-woven cotton and synthetic fabric media,
media support grid and enclosing frame. The filter shall be listed by
Underwriters’ Laboratories as Class 2.
2.
Filter media shall have an average efficiency of 25-30% on ASHRAE Test
Standard 52-76. It shall have an average arrestance of 90-92% in accordance
with the test standard.
3.
The effective filter media shall not be less than 4.6 ft2 of
media per 1.0 ft2 of filter face area and shall contain not less than
15 pleats per linear foot.
4.
Holding frames shall be face loading type,16 ga. galvanized steel and
shall be equipped with gaskets and four spring type positive fasteners.
5.
Filters shall be as specified complete with holding frames.
6.
Each filter bank shall be furnished with a pressure differential gauge,
with two static pressure tips and vent valves. Gauges shall be factory mounted
on unit casing. Static pressure tips and valves shall be factory piped.
I.
Dampers
1.
Dampers shall be low leakage, air foil blade type. Frames shall be
constructed of 6063T5 extruded aluminum hat channel with hat mounting flanges on
both sides of the frame.
2.
Blades shall be airfoil type extruded aluminum with integral structural
reinforcing tube running the full length of each blade. Blade edge seals shall
be extruded vinyl double edge design. Blade seals shall be locked in extruded
blade slots and be easily removable.
3.
Bearings shall be non-corrosive two piece molded synthetic. Axles shall
be square or hexagonal only. Linkage shall be concealed in the frame.
4.
Damper performance must be based on AMCA Standard 500 in an AMCA approved
laboratory.
5.
Dampers shall be as specified.
6.
Damper actuators shall be furnished and installed by the air temperature
control contractor 50 degrees F mean temperature.
J.
Silencers
1.
Inlet Silencer: The inlet silencer shall be designed to distribute
airflow from low velocity at the inlet to the velocity of the fan annular area
at the outlet, within the specified energy and horsepower requirements.
The design shall minimize
the total pressure losses by utilizing good aerodynamic principals and
fundamentals that reduce the noise created by the fan system.
The silencer shall have shed
resistant media protection and acoustic absorbing perforated surfaces.
Silencer pressure drop
shall not exceed scheduled performance and the insertion loss shall not be less
than specified.
2.
Discharge Silencer: The silencer shall aerodynamically diffuse the fan’s
discharge air to allow a minimal total pressure loss.
The silencer design shall
incorporate good engineering fundamentals to develop an efficient conversion of
velocity pressure to static pressure.
The silencer shall have shed
resistant media protection and acoustic absorbing perforated surfaces.
Silencer pressure drop shall
not exceed scheduled performance and the insertion loss shall not be less than
specified.
3.
Combustion rating: AHU materials
shall have maximum combustion ratings as noted below when tested in accordance
with ASTM E84, NFPA 255 or UL 723.
AHU materials including
glass fiber:
Flamespread
Classification: 15
Smoke Development
Rating: 5
AHU materials including
glass fiber, film liner and acoustical spacer:
Flamespread
Classification: 20
Smoke
Development: 45
Part 4 - Execution
4.1
Installation of Air Handling Units
A.
General:
Install air-handling units where indicated on the contract drawings, in
accordance with the equipment manufacturers published installation instructions.
B
Access:
Provide access space around the air handling units for service as indicated on
the drawings, but not less than that recommended by the manufacturer.
C.
Support:
Install floor-mounted air handling units on 4” high concrete housekeeping pad,
4” larger on each side than unit base.
D.
Field Adjustments: Adjust fan vibration isolators in accordance with
manufacturer’s instructions.
E.
Electrical
Wiring: Install
electrical devices furnished by manufacturer but not specified to be factory
mounted. Verify that electrical wiring installation is in accordance with
manufacturer’s submittal and installation requirements of Division 16 sections.
F.
Piping
Connections:
Provide piping, valves, accessories, gauges, supports, and flex connections as
indicated on the contract drawings. Locate freezestats and trap drain-pan
connections according to manufacturer’s recommendations.
G.
Duct
Connections:
Provide ductwork, accessories, and flex connections as indicated on the
drawings.
4.2
Testing
A.
General:
Upon completion of air handling unit installation, start-up and operate
equipment to demonstrate capability and compliance with contract document
requirements. Field correct any deficiencies and retest to demonstrate
compliance.
4.3
Extra Stock
A.
Filters:
Provide one extra set of filters for each air-handling unit. Install new
filters at completion of air handling system work, and prior to testing,
adjusting and balancing work. Do not operate fans unless filters are in place.
|